中英文版柴油發(fā)電機(jī)房進(jìn)風(fēng)量計(jì)算Generator room wind intake calculation

作者:中威網(wǎng)絡(luò)部 來源:移動(dòng)式沃爾沃靜音箱100KW柴油發(fā)電機(jī)組 發(fā)表時(shí)間:2020-02-26 02:01:42 查看:
柴油發(fā)電機(jī)房采用清潔式通風(fēng)時(shí),應(yīng)按下列規(guī)定計(jì)算進(jìn)、排風(fēng)量:

When diesel generator room adopts clean ventilation,Calculate the intake air volume and the exhaust air volume as follows:
柴油發(fā)電機(jī)
1.當(dāng)柴油發(fā)電機(jī)房采用空氣冷卻時(shí),按消除柴油發(fā)電機(jī)房?jī)?nèi)余熱計(jì)算進(jìn)風(fēng)量;

1. When the diesel generator room adopts air cooling, the intake air volume is calculated by eliminating the residual heat in the diesel generator room;

2.當(dāng)柴油發(fā)電機(jī)房采用水冷卻時(shí),按排除柴油發(fā)電機(jī)房?jī)?nèi)有害氣體所需的通風(fēng)量經(jīng)計(jì)算確定。有害氣體的容許含量。篊O為30mg/m3,丙烯醛為0.3mg/m3,或按大于等于20m3/(kW·h)計(jì)算進(jìn)風(fēng)量;

2.When the diesel generator room is water-cooled, the permissible amount of harmful gases determined by removing the amount of ventilation required for harmful gases in the diesel generator room is: CO is 30 mg/m3, and acrolein is 0.3 mg/m3. Or calculate the amount of air intake greater than or equal to 20 cubic meters/(kilowatt-h);


3.排風(fēng)量取進(jìn)風(fēng)量減去燃燒空氣量。

柴油機(jī)燃燒空氣量,可根據(jù)柴油機(jī)額定功率取經(jīng)驗(yàn)數(shù)據(jù)計(jì)算:7m3/(kW·h)。清潔通風(fēng)時(shí),柴油機(jī)所需的燃燒空氣直接取用發(fā)電機(jī)房室內(nèi)的空氣;隔絕防護(hù)時(shí),應(yīng)從機(jī)房的進(jìn)風(fēng)或排風(fēng)管引入室外空氣燃燒,但吸氣系統(tǒng)的阻力不宜超過1kPa。

3.Exhaust volume is equal to wind intake minus combustion wind quantity.

The amount of diesel engine combustion air can be calculated based on the diesel engine rated power and empirical data: 7m3/(kW·h).For clean ventilation, the combustion air required by the diesel engine directly uses the air in the generator room. In the case of isolation and protection, outdoor air shall be introduced from the air inlet pipe or exhaust pipe of the engine room, but the resistance of the air intake system should not exceed 1 kPa.